Features:
  • Easy product selection
  • Fast, easy actuator installation-no linkage or tools required.
  • Two-position-On/Off Spring Return (Jumper selectable)
  • RoHS Compliant (VBS Assemblies)
  • Reach Compliant
Unit of Measure

Specifications

Type

N/A Automatic Temperature Control

Fail Safe

N/A Model A2X0AXX / 2 Position On/Off Spring Return

Manufacturer

N/A Schneider / Erie Actuators

Control Signal

N/A Two Position

Spring Return Action (Valve Normal Position)

N/A Normally Open

VA @ 24 Vac

N/A 3.5

VA @ 24 Vdc

N/A 1.8

Leads

N/A 18 in. (45 cm) Appliance Wire

Stroke Time

N/A 50 s

Spring Return Time

N/A 30 s
End Switch1 N/A SPST

Specification No.

N/A COMP-SPEC-ATC6-001, COMP-SPEC-ATC6-002

Application

N/A The A1 series actuators are direct coupled to the valve and accept two position, floating or proportional control signals from a DDC system, controller or thermostat for control of hot or chilled water, or solutions of up to 60% glycol. Typical applications include VAV reheat, fan coil units, hot and chilled water coils in the air handling units, heat pumps and unit ventilators.

Actuator Specifications

N/A

  • Voltage - 24Vac + 25%, -15% @ 50/60 Hz
  • Power Requirements
  • Manual Operating Lever/Position Indicator - Standard on all models
  • Control Signal - 2-Position
  • Timing, Full Open to Full Close
  • Materials - Blue Thermoplastic base and cover.
  • Approved for use in air plenums.
  • Shipping & Storage Temperature Limit -40 to 160º F (-40 to 71º C)
  • Operating Temperature Limit at max fluid temp.
    • Two Position - 32 to 169º F (0 to 76º C)
  • Humidity - 5 to 95% relative humidity, non-condensing
  • Location - NEMA 2, IEC IP31

Application Notes

N/A Two-Position Spring Return Actuators, when powered, the actuator moves to the desired position, tensing the spring return system. When power is removed the actuators returns to the normal position. Two position spring return actuators can be purchased with an optional built-in auxiliary SPDT end switch for interfacing or signaling; for example, zone pump burner control.

Agency Listings

N/A

UL873 Underwriters Laboratories (File #E9429 Category Temperature indicating and Regulating Equipment).
CUL Listed for use in Canada by Underwriters Laboratories, Canadian Standards C22.2 No. 24.
European Community EMC Directive (89/336/EEC). Low Voltage Directive (72/23/EEC).
Australia This product meets requirements to bear the C-Tick Mark according to the terms specified by the Communications Act of 1992.
Plenum Rating Plenum rated per UL E9429 Vol 2 Section 40.
CRN Number #OCO970.9087TN.
RoHS Compliant A1 actuators comply with European Directive 2002/95. Please consult factory for part number specific compliance
REACH Compliant Compliant as defined in Article 33 of the REACH regulation No. 1907/2006.

  • 1 Contact rating 24Vdc - 250Vac